ISHRAE 10001:2019 · ASHRAE 62.1

Indoor air quality testing in Navi Mumbai and Mumbai

IAQ surveys for data centre NOCs, control rooms, offices and labs. We measure what people breathe, find where ventilation is falling short, and give your facilities team a clear list of fixes.

Panel 8 parametersLogging full working dayReport 5 working days

Why IAQ matters in a building full of machines

A data centre is designed for servers, but the NOC, security and office areas are occupied 24 hours a day. These rooms are often small, sealed and running on recirculated air. CO₂ builds up overnight shifts, and staff report headaches and drowsiness long before anyone checks the air.

Mumbai's outdoor PM2.5 also rises sharply between November and February. If your fresh-air filtration is not sized for it, that dust ends up inside, on people and on equipment.

What we do on site

  • Agree zones and occupancy with your facilities team, and log the HVAC mode during the test
  • Log each parameter continuously at breathing height, 1.1 m seated or 1.7 m standing
  • Take an outdoor reference at the same time, so we can separate indoor sources from outdoor air
  • Check fresh-air dampers, filter condition and supply airflow where access allows
Multi-parameter indoor air quality monitor on a tripod in a network operations centre
A multi-parameter IAQ analyser logs CO₂, particulates and VOCs together, so one event (a crowded shift change, a DG test) shows up across all channels.
Technician checking indoor air quality with a handheld meter near a ceiling air diffuser in an office
Spot checks near supply diffusers and at desks show whether fresh air is reaching the people in the room.

Common reference values

Your project specification or rating system sets the final limit. These are the reference points most Indian projects start from.

ParameterCommon referenceSourceUsual cause when high
CO₂≤ 1,000 ppmASHRAE 62.1 practice, ISHRAE 10001Too little fresh air for occupancy
PM2.5≤ 15 µg/m³ (24 h)WHO 2021 guidelineOutdoor dust, poor filtration
PM2.5≤ 60 µg/m³ (24 h)India NAAQS 2009Regulatory ambient limit
PM10≤ 100 µg/m³ (24 h)India NAAQS 2009Construction dust, open doors
TVOC≤ 500 µg/m³LEED and WELL practiceNew furniture, paints, cleaning chemicals
Formaldehyde≤ 100 µg/m³ (30 min)WHO guidelinePressed wood, adhesives
CO≤ 2 mg/m³ (8 h)India NAAQS 2009DG or vehicle exhaust entering
Temperature / RH23 to 26 °C / 40 to 60%Comfort practiceHVAC setpoints, latent load

IAQ testing FAQs

What parameters are included in an IAQ test?
Our standard panel is carbon dioxide (CO₂), carbon monoxide (CO), PM2.5, PM10, total volatile organic compounds (TVOC), formaldehyde (HCHO), temperature and relative humidity. Ozone, NO₂ and lux can be added.
How many points do you test in an office?
As a starting point, one point per 500 m² of occupied floor or per air handling zone, whichever gives more points, plus one outdoor reference. Meeting rooms and NOC rooms with high occupancy get their own points.
Can IAQ results support IGBC, LEED or WELL certification?
Yes. We test against the limits and protocol your rating system asks for and report in its format. Tell us the credit you are targeting so we use the right sampling duration and averaging time.
Is a one-day test enough?
A one-day test during normal occupancy shows whether there is a problem. CO₂ and PM levels change through the day, so we log continuously across the working day and report peaks as well as averages. For recurring complaints we suggest a 7-day logged survey.

Request a test plan

Tell us the site, the rooms and the standard you have to meet.

We reply within one working day with a sampling plan, the number of test points, turnaround and a fixed quote. Site visits across Mumbai, Navi Mumbai, Thane and Pune, and pan-India on project basis.