IS 10500:2012 · ISO 11731 · ASHRAE 188
Water, cooling tower and Legionella testing
One lab for every water stream in a data centre: potable, cooling tower, chilled water, humidifier feed, STP outlet, fire water and liquid cooling fluid. Chemistry and microbiology are both done at our Navi Mumbai lab.
Why an independent water test matters
Most sites rely on the water treatment vendor's own test kit. That is fine for daily control, but the same company that doses the chemicals is reporting whether the dosing works. An independent lab result, taken on the same day, is how you check that the numbers match.
Cooling towers are the main Legionella risk in a data centre. Warm water, sunlight, nutrients and aerosol drift make them ideal for bacterial growth. A positive result found early is a disinfection and a review. Found late, it is a health incident.
Chilled water loops fail more slowly. Rising iron and copper, falling inhibitor and bacterial growth tell you the loop is corroding long before a pipe leaks under the raised floor.


Water streams and test panels
Panels can be adjusted to your water management plan or consent conditions.
| Stream | Key parameters | Reference |
|---|---|---|
| Potable / drinking | pH, turbidity, TDS, hardness, chloride, iron, residual chlorine, total coliform, E. coli | IS 10500:2012 |
| Cooling tower | pH, conductivity, TDS, calcium and total hardness, M-alkalinity, chloride, silica, iron, free chlorine, total bacterial count, Legionella; LSI and RSI scaling indices | Water treatment plan, ASHRAE 188, ISO 11731 |
| Chilled water (closed loop) | pH, conductivity, iron, copper, inhibitor residual (nitrite or molybdate), total bacterial count | Treatment vendor specification |
| Humidifier feed | Conductivity, hardness, silica, total bacterial count | Humidifier manufacturer limits |
| STP / ETP treated water | pH, BOD, COD, TSS, oil and grease, faecal coliform | MPCB consent conditions |
| Fire water tank | pH, turbidity, hardness, iron, bacterial count | Fire system maintenance practice |
| Liquid cooling fluid | Glycol %, pH, conductivity, inhibitor, dissolved metals, particle cleanliness | ISO 4406, CDU manufacturer limits |