Particle count testing and cleanroom classification

Airborne particle surveys for data halls, MMRs, UPS and battery rooms, and ISO-classified cleanrooms. Used for annual compliance, post-cleaning verification, and pre-IST handover after construction.

Sizes 0.3, 0.5, 1.0, 5.0, 10 µmFlow 2.83 L/min and 28.3 L/min countersReport 5 working days

Why data centres count particles

Servers pull large volumes of room air through their chassis. Fine dust settles on heat sinks and fans, raising component temperatures. Some dust is worse than others: zinc whiskers shed from old galvanised raised-floor tiles are conductive, and dust carrying salts or sulfates absorbs moisture once room humidity passes its deliquescence point, which can cause leakage currents and shorts.

ASHRAE TC 9.9 therefore asks that data centres stay at ISO 14644-1 Class 8, with MERV 8 filtration on recirculated air and MERV 11 or MERV 13 on outdoor air. A particle survey tells you whether your filters, pressurisation and cleaning are holding that line.

How we run the survey

  • Occupancy state agreed first. As-built, at-rest or operational, recorded on the certificate, because the same room gives very different counts in each.
  • Locations from Table A.1 of ISO 14644-1:2015, based on floor area, then marked on your layout drawing with a location ID.
  • Sample volume calculated so that at least 20 particles would be counted at the class limit for the largest particle size considered, with a minimum of 2 litres and 1 minute per sample.
  • Pass per location. The 2015 edition dropped the 95% upper confidence limit calculation. Every location must meet the limit on its own.
Handheld laser particle counter showing channel counts in a data centre cold aisle
Handheld laser particle counters log six channels at once. Each reading is stored with location ID, time and instrument serial number.
Technician taking a particle count in a raised-floor data hall
A survey point in the cold aisle. Each reading is logged against a location ID on your layout drawing.

ISO 14644-1:2015 class limits

Maximum particles per cubic metre of air, for particles equal to or larger than the stated size.

ISO class≥ 0.3 µm≥ 0.5 µm≥ 1.0 µm≥ 5.0 µmTypical use
Class 510,2003,520832n/aAseptic zones, semiconductor
Class 6102,00035,2008,320293Electronics assembly
Class 7n/a352,00083,2002,930Pharma secondary, DC handover (some operators)
Class 8n/a3,520,000832,00029,300Data centre white space (ASHRAE)
Class 9n/a35,200,0008,320,000293,000Ambient-controlled rooms

Source: ISO 14644-1:2015, Table 1. "n/a" means the standard does not set a limit at that size for that class.

What your report contains

  • Floor plan with every sample location and its ID
  • Raw counts per channel, sample volume and timestamp for each location
  • Pass or fail per location against the class you specified
  • Instrument serial numbers, calibration dates and certificate references
  • Observations: open floor tiles, missing blanking panels, door seals, construction debris
  • Recommended actions and a suggested re-test interval

Most operators test every 6 or 12 months, and always after construction work, a filter change programme or a deep clean.

Pre-IST handover tip. Contractors often clean once, test once and hand over. Ask for the test after the final clean, with CRAHs running and the floor closed, and ask that the sample points include the area near cable cut-outs. That is where construction dust hides.

Particle testing FAQs

What ISO class should a data centre meet?
ASHRAE TC 9.9 recommends that data centres meet ISO 14644-1 Class 8, which allows up to 3,520,000 particles of 0.5 µm and larger per cubic metre. Some operators set Class 7 for specific rooms or for handover after construction. Use the class written in your design basis or customer contract.
How many sample locations are needed?
ISO 14644-1:2015 replaced the old square-root-of-area rule with Table A.1, which sets the minimum number of locations from the room's floor area. A large data hall needs more points than the old formula gave. We take the area from your drawings and add points near CRAH returns, doors and cable cut-outs.
Is a particle count enough to prove a data hall is clean?
It proves the air is clean at the time of the test. It does not prove surfaces, under-floor voids or ceiling plenums are clean. For handover after construction or deep cleaning we pair airborne counts with surface checks and visual inspection.
Do you certify cleanrooms for pharma and electronics?
Yes, for ISO 14644-1 classification of non-viable particles at-rest and in-operation. Viable (microbial) air sampling for GMP grades is outside our current scope.

Request a test plan

Tell us the site, the rooms and the standard you have to meet.

We reply within one working day with a sampling plan, the number of test points, turnaround and a fixed quote. Site visits across Mumbai, Navi Mumbai, Thane and Pune, and pan-India on project basis.

Emailinfo@coloenvirolabs.com